Skip Navigation LinkslindQST / Damper Calculator
Product name
Duct connection size
Voltage
Motor type
Airflow
qv*
Adjustment pressure
Δp
Pa
Description

DTBCU-100-24-TF

Add to project
  • Product information
  • Results
  • View in 3D

Motorized shut-off damper
  • Images
  • Product description
  • Related documents
  • Videos
MISSING

The DTBCU is a spring return damper which closes if the electrical power is off. The damper can be ordered with the following control option.

24 or 230 V on off motor

24 V motor with 2-10 V analog control signal
(motortype -SR)

24 V motor with data bus control; Modbus, BACnet, MP-Bus
(motortype - MOBA)

The motor has overload protection and stops automatically when the blade has reached its end stop. Although the current is connected, the motor is not damaged if blocked.

When the power is cut, the damper closes when the drive motor freewheels and the return spring pulls the blade back to its original position.

If you want the damper to open instead of close, you can undo the two nuts on the spindle clamp, turn the spindle 90°and tighten the nuts again.

In outdoor installation, the motor should be protected from direct UV radiation.

The motor is installed at a distance from the damper, which makes it easy to insulate the ventilation duct.

There is a separate assembly, measuring balancing and maintenance instruction for this product.


MISSING
Total pressure loss
Δpt
Pa
Sound power level
LwA
dB(A)
Velocity
v
m/s
Damper angle
°
deg
  • Pressure and sound power diagram
    MISSING
    Hz 63 125 250 500 1K 2K 4K 8K
    Lw 61 56 53 47 40 34 26 18

© Copyright 2023, Lindab AB. All rights reserved. lindQST.com is owned by Lindab AB all images, technical data and other material found on this site belongs to Lindab AB. Please contact Lindab if you wish to use our material in other matters.